Online UPS

» Online UPS

Online UPS - High frequency

PS 1000 ONL / 2000 ONL / 3000 ONL / 6000 ONL / 10000 ONL / 20000 ONL UPS models are ideal for Data processing center, computing center, ISP, Banking, Securities, Communications.

  • True on-line, Zero Transfer Time, dual conversion design.
  • Sine wave pulse width modulation (SPWM).
  • High Frequency Technology used for Higher Efficiency.
  • Wide Input voltage window.

Available in in six models: PS 1000 ONL / 2000 ONL / 3000 ONL / 6000 ONL / 10000 ONL / 20000 ONL

True Online UPS with Double-conversion
Wide Input Voltage Range (110-300VAC)
Active Input Power Factor Corrector
Selectable Output Voltage
1/4/5/8A Smart 3 Stage Battery Charger*
Generator compatible
RS232/USB/LAN (SNMP) port*
ECO mode operation for energy saving*
Programmable power management outlet*
Emergency power off (EPO) function*
Optional N+X Parallel Redundancy*

  PS 1KVA
ONL
PS 2KVA
ONL
PS 3KVA PS 6KVA ONL PS 6KVA ONL(96V) PS 10KVA ONL PS 20KVA ONL
Capacity VA/W 1000 / 800W 2000 / 1600W 3000 / 2400W 6000 / 4200W 6000 / 4800W 10000 / 8000W 20000 / 16000W
Input
Voltage Range
Lo Transfer 160/140/120/110VAC +/-5%
based on load percentage
176VAc +/3% @ Full Load
110VAC+/-3% @50% Load
Lo Resume 175VAC +/-5% 186VAC+/-3% @ Full Load
120VAC +/-3% @ 50% Load
Hi Transfer 300VAC +/-5% 280vac /-3% 300VAC /-3%
Hi Resume 290VAC +/-5% 270vac+/-3% 290VAC +/-3%
Frequency 47 to 53Hz or 57 to 63 Hz (Auto sense) 46 to 54Hz or 56 to 64Hz
Phase Single Phase in Single Phase out with Neutral and Ground 3ph +N + Ground
Power Factor >>= 0.98 >=0.99 @ Full Load
Output
Voltage 208/220/230/240VAC (Selectable)
Range +/- 3% +/- 1%
Frequency
Mains 47 to 53 Hz or 57 to 63 Hz
Battery 50Hz +/-0.25Hz or 60Hz +/-0.3Hz 50 or 60Hz +/-0.1Hz
Over load (Batt)
100-110% Audible Warning Shutdown after 30 sec
110-130% Shutdown after 30 sec Shutdown after 10 sec
>130% Shutdown immediate Shutdown after 1 sec
Current Crest Ratio 3:1
Harmonic Distortion
Linear Load <= 3% <= 4% THD <= 3% <= 2%
Non-Linear <= 6% <= 7% THD <= 6% <= 5%
Transfer Time
Change over Zero
To Bypass 4ms Zero
Waveform Pure Sine wave
Efficiency
On Mains >85% >88% >89%
On Battery 86%
Battery
DC Bus Voltage 24 48 72 96 240
Internal Battery 12V/7AH* 2 4 6 8 20
External Battery 25-100Ah 25-160Ah 25-160Ah 25-100Ah
Charging Current* 1A or 5A 1/2/4/8A 1 or 5A 8A 4A 4/8A
Charging Voltage (+/-1%) 27.4V 54.7V 82.1V 109.4V 273V
Indications
LCD Panel UPS Status, Load Level, Battery Level, Input V, Output V, Discharge Time & Fault
Physical
Dimensions (DxWxH) mm 400x146x205 397x145x220 421x190x318 592x250x576
Net Weight (kgs)
With Battery 9.5 17.5 28 Not Available
W/o Battery 5 9 13 14.3 25 28 37
Environment
Operating Humidity 20-90% RH @ 0-40C (non Condensing)
Noise Level @ 1 meter Less than 45dBA < 55dBA < 58dBA
Management
RS232 Port Supports Windows 2000/2003/XP/Vista/2008/Windows 7, Linux, Unix and Mac
Optional Intelligent Slot Power Management from SNMP manager and web browser
* In selected Models, Specifications subject to change without prior notice.