Powersafe UPS

Longer Backup UPS with AVR

Specifications

PS 600L / 1000L / 2000L UPS models are ideal for SOHO environment.

  PS 600L PS 1000L PS 2000L
Capacity VA/W 600VA/360W 1000VA/600W 2000VA/1200W
Input
Voltage Range 140-300VAC
Frequency Range 50 or 60HZ (Auto Detect)
Output
Voltage 220V AC +12% to -18%
Frequency 50 or 60HZ +/-0.1HZ
Waveform Modified Sinewave
Transfer Time 4-8mS typical, 14mS max
Battery
Type Lead-acid or maintenance Free
Voltage 12V 12V 24V
Charging Current 10A 10A 10A
Batt. Capacity 50Ah to 100AH
Backup Time (Refer Backup Time Chart below)
On 190Ah Full Load 6 Hours 3h40m 3h40m
Indicator
Mains Mode Green Lighting
Battery Mode Yellow Lighting
Charging Mode Green Flashing
Over Load Red Flashing every half second
Fault Red Lighting
Audible Alarm
Battery Mode Sounding Every 10 sec
Low Battery Sounding Every 2 sec
Over Load Sounding Every 0.5 sec
Fault Continuous Sounding
Protection Discharge, overcharge, and overload protection
Physical
Dimensions (WxDxH mm) 402X117X222
Net Weight (kgs) 4 4.9 6.5

Backup Time Chart

  Load 1 PC 2 PC 3 PC 4 PC 5 PC 6 PC
PS-600L
Battery: 12V x 1
DC Bus: 12V
Charger: 10 Amp
65AH 3h15m 1h20m Go
for
1000L
 
88AH 5h 2h15m
120AH 8h 3h20m
150AH 9h30m 4h30m
190AH 14h 6h
PS-1000L
Battery: 12V x 1
DC Bus: 12V
Charger: 10 Amp
65AH 3h15m 1h20m 45m
88AH 5h 2h15m 1h10m
120AH 8h 3h20m 2h
150AH 9h30m 4h30m 2h30m
190AH 14h 6h 3h40m
PS-2000L
Battery: 12V x 2
DC Bus: 24V
Charger: 10 Amp
65AH 7h30m 3h15m 2h 1h20m 1h 48m
88AH 10h 5h 3h 2h15m 1h30m 1h20m
120AH 17h 8h 4h40m 3h20m 2h30m 1h50m
150AH 22h 9h30m 6h 4h30m 3h20m 2h30m
190AH 30h 14h 9h 6h 4h40m 3h40m

Go back